This is another step forward in the reduction of wiring and components.
This is in fact the forerunner of a new generation of controllers that combine the control and power components of the unit.
As well as the typical advantages of the plug-in series, one feature worth highlighting is the management of up to two 2 Hp compressors, with the start of the second compressor delayed from the first by 4 seconds.
The defrost relay is rated for up to 3200 W.
Technical specifications
Power supply
230 Vac/dc (-15% to +10%), 50/60 Hz
Power input
4 A
Control range
-50T90 °C, resolution 1 °C
Type of probe
NTC or PTC according to the model
Outputs
defrost relais: 14 (2) A res.;
fan relais: 6 (2) A res.;
2 Hp compressor relais: 10 (10) A
Maximum rated current per terminal
12 A
Dimensions of plastic box (power board)
190x140x70 mm
Connections
screw terminals or plug-in connectors
Installation
panel mounting with front housing or rear bracket (terminale); wall mounting,
4 screws positioned at 101x151 mm (power board)